![]() |
CENTRAL CALAVERAS FIRE &
RESCUE
PROTECTION DISTRICT
P.O. Box 2, 19927 Jesus
Maria Road, Mountain Ranch, Ca 95246 Office: (209) 754-4330 FAX: (209) 754-3906 www.centralcalaverasfire.org |
![]() |
(REQUIREMENTS)
The following are general requirements of the
Central Calaveras Fire & Rescue Protection District for residential home
sites. These comments are for site plans only. Plans submitted for approval
shall represent all requirements that apply. All of the following comments
shall be printed on a comment sheet attached to the plans submitted for
approval.
The address of the proposed residential home shall
be posted and visible from the roadway fronting the property. Whenever the
numbers on the building will not be clearly visible from the access roadway,
the numbers will be placed at the access roadway and the driveway. Address
numbers shall be visible from both directions of travel on the roadway fronting
the property. Said numbers shall be a minimum 3 inch letter height, 3/8 stroke,
reflectorized, and contrast with their background, or may be a minimum 5 inches
high and contrast with their background.
On site water supply for firefighting shall be as
follows for one and two family dwellings:
For new subdivisions when more than four parcels
are created the minimum fire flow, through approved fire hydrants, and shall be
1,000 gallons per minute at 20 pounds residual pressure.
The minimum fire flow may be reduced when the size of all proposed structures are less than 3,600 square feet. Fire flow for dwellings having a fire area in excess of 3,600 square feet shall not be less than that specified in Table A-III-A-1 of the 1997 Uniform Fire Code. All proposed water supplies shall come from a reliable source such as an fixed underground water distribution system or a static water system equaling or exceeding the National Fire Protection Assn. (NFPA) Standard 1142, “Standard on Water Supplies for Suburban and Rural Fire Fighting”. On site water supply for firefighting is not required for lots splits or minor subdivisions of 4 or less.
EXCEPTION: A reduction in fire flow
of 50 percent, as approved by the fire chief, is allowed when the building is
provided with an approved automatic sprinkler system.
Driveways serving one parcel but no more than five
structures shall be a minmium of 12 feet in width. Vertical clearance shall be
13 feet 6 inches for the width of the road. For the purpose of this section,
roadway width shall mean driving surface. Curb and gutter is not included in
the roadway width. Driveways exceeding 150 feet in length, but less than 800
feet in length, shall provide a turnout near the midpoint of the driveway. A
turnaround shall be provided at all building sites on driveways over 300 feet
in length and shall be within 50 feet of the building. All roadways and access
roads shall be completed previous to any building construction. (See
Attached Details)
Driveway surfaces shall be paved or similar
approved surfaces, capable of supporting a 40,000 lb load.
The grades for all roads, streets, private lanes
and driveways shall not exceed 16 percent.
No roadway shall have a horizontal outside radius
curvature of less than 42 feet.
Turnarounds are required on driveways and dead end
roads as specified. Cul-de-sacs radius shall be 42 feet of driving surface.
Curb and gutter is not included in the cul-de-sacs radius. If a hammerhead/T is
used, the top of the (T) shall be a minimum of 60 feet in length. Curb and
gutter is not included in the hammerhead length.
Gate entrances shall be at least two feet wider of
the traffic lane serving that gate.
All gates providing access from a road to a
driveway or private road shall be at least 30 feet from the roadway and open to
allow a vehicle to stop without obstructing traffic on that road. Gates shall
be accessible to the fire district by approved electric key switch, strobe
entry, person gate and standard keypad access. (See Attached Details)
Driveway Bridges
Bridges shall have a minimum load of 40,000 pounds
and be no narrower than the driving portion of the road serving each end.
To allow for wildland fire defensible space, thirty
feet shall be maintained as side and rear building setbacks on lots larger than
one acre.
Open areas around residential homes shall be
maintained in a fire safe condition. The homeowner shall be responsible to
remove dead and dry vegetation at least 30 feet from all non-fire resistive
structures. This includes all homes, outbuildings and wooden fences.
The final plans shall be approved only when stamped
and/or signed by authorized Central Calaveras Fire District personnel.
Final acceptance of the project is subject to
inspection and testing from the Central Calaveras Fire District. 72 hour notice
require previous to inspection and testing.
Attached Details Not Drawn to Scale:
The following are general requirements of the Central Calaveras Fire Protection District for major and minor residential subdivision sites. These comments are for site plans only. Plans submitted for approval shall represent all requirements that apply. All of the following comments shall be printed on a comment sheet attached to the plans submitted for approval.
Roadways
and Access Routes
The minimum number of access roads serving
residential development (s) shall be based on the number of dwellings units
served and shall be as follows:
1 to 75 units, one public access road and emergency
access/egress roads as required by dead end road requirement.
76 plus units, two public access roads and
emergency access/egress roads as required by dead end road requirement.
Roadways serving four or less parcels shall be no
less than 20 feet in width. Roadways serving five parcels or more shall meet
Calaveras county standards but shall be no less than 24 feet in width.
Driveways serving one parcel but no more than five structures shall be a
minimum of 12 feet i width. Vertical clearance shall be 13 feet 6 inches for
the width of the road. For the purpose of this section, roadway width shall
mean driving surface. Curb and gutter is not included in the roadway width.
Emergency access/egress roadways shall meet Calaveras county standards but
shall be no less than 20 feet in width. Emergency access/egress roadways shall
be marked with approved signs stating “Emergency Fire Road”. All required
roadways, access roads and water supplies for fire protection shall be
installed and made serviceable prior to and during the time of construction. (See
Attached Details)
There shall be no parking on roadways 30 feet or
less in width, cul-de-sac radius less than 42 feet or hammerhead turn around
less than 30 feet in width. Parking will be allowed on one side of the road on
roadways 30 feet to 36 feet. On Roadways over 36 feet parking will be allowed
on both sides. When the proposed lots are larger than one acre, and the roadway
width restricts parking, yellow centerlines and white lane defining lines shall
be provided outlining two 12-foot driving lanes. When the proposed lots are
smaller than one acre but larger than one-quarter acre, and the roadway
restricts parking, “No Parking Fire Lane” signs shall be posted every 200 feet.
When parking is allowed on one side of the road, and the proposed lot size
allows for no parking signs only, painted designated parking areas will be provided
on the side of the street where parking will be allowed. When the proposed lots
are smaller than one-quarter acre, and the roadway width restricts parking, “No
Parking Fire Lane” signs shall be posted every 200 feet and curbs to be painted
red with “No Parking Fire Lane” stenciled on them. (See Attached Details)
Roadway Surface
Roadway and emergency access roadway surfaces shall
be paved, capable of supporting a 40,000 lb load. Driveway surfaces shall be
paved or similar approved surfaces, capable of supporting a 40,000 lb load,
IAW-2001 CFC, Cal. Co. Ord 8.10.
The grade for all roads, streets, private lanes and
driveways shall not exceed 16 percent, IAW-2001CFC, Cal. Co. Ord 8.10.
No roadway shall have a horizontal outside radius
curvature of less than 42 feet or an inside radius curvature of less than 27
feet. (See Attached Details)
Turnarounds are required on driveways and dead end
roads as specified. Cul-de-sac radius shall be 42 feet of driving surface. Curb
and gutter is not included in the cul-de-sac radius. If a hammerhead/T is used,
the top of the (T) shall be a minimum of 60 feet in length. Curb and gutter is
not included in the hammerhead length. (See Attached Details)
The maximum length of a dead-end road shall not
exceed cumulative lengths, regardless of the number of parcels served.
Parcels proposed less than 1 acre 800-feet
Parcels proposed 1 acre to 4.99 acres 1320-feet
Parcels proposed 5 acres to 19.99 acres 2640-feet
Parcels proposed 20 acres or larger 5280-feet
Each dead-end road shall have a turnaround
constructed at its terminus. (See Attached Details)
All driveways shall provide a minimum 12-feet
traffic lane and unobstructed vertical clearance of 13 feet 6 inches along its
entire length. Driveways exceeding 150-feet in length, but less than 800 feet
in length shall provide a turnout near the midpoint of the driveway. A
turnaround shall be provided at all building sites on driveways over 300 feet in
length and shall be within 50 feet of the building. (See Attached Details)
Gates proposed at required access and egress
roadways shall be at least two feet wider than the width of the traffic lane
serving the gate. All gates providing access from a public road to a driveway
or private road shall be located at least 30 feet from the serving public
roadway and open to allow a vehicle to stop without obstructing traffic. Gates
shall be accessible to the fire district by approved electric key switch,
strobe entry, person gate and standard keypad access. Gates shall allow
automatic egress for community members in the event of an emergency. Gates
shall automatically open and remain open during power outages. (See Attached
Details)
Bridges shall have a minimum load of 40,000 pounds
and be no narrower than the driving portion of the road serving each end. Major
ingress/egress roads in subdivisions shall have a minimum load limit of 80,000
pounds.
On site water supply for firefighting shall be as
follows for one and two family dwellings. For new subdivisions when more than
four parcels are created the minimum fire flow, through approved fire hydrants,
and shall be 1,500 gallons per minute at 20 pounds residual pressure. The
minimum fire flow may be reduced to 1,000 gallons per minute when the size of
all proposed structures are less than 3,600 square feet. Fire flow for
dwellings having a fire area in excess of 3,600 square feet shall not be less
than that specified in Table A-III-A-1 of the 1997 Uniform Fire Code. All
proposed water supplies shall come from a reliable source such as a fixed
underground water distribution system or a static water system equaling or
exceeding the National Fire Protection Assn. (NFPA Standard 1142) “Standard on
Water Supplies for Suburban and Rural Fire Fighting”. On site water supply for
firefighting is not required for lot splits or minor subdivisions of 4 or less.
EXCEPTION: A reduction in fire flow of 50 percent, as approved by the fire
chief, is allowed when the building is provided with an approved automatic
sprinkler system.
Hydrants shall be wet barrel type with two 2-½ inch
discharges and one 4-½ inch discharge. with individual valves for each
discharge. (RICH 960 or equivalent). Two way blue reflective pavement markers
shall be placed in the roadway (eight inches from the center line on the
hydrant side) at each location. The area around the hydrant will be kept clear
of obstructions including fences, trees and shrubs. The center of the lowest
discharge shall be a minimum of 18 inches and maximum of 24inches off the
ground. Hydrants shall be a maximum of 6 feet from the driving surface when
sidewalks are proposed otherwise hydrants shall be a maximum of 2 feet from the
driving surface. Water supply and hydrants to be provided previous to any
building construction. Final acceptance of the water supply system shall be
granted only after testing and inspection by the fire district. Water supply
system testing and inspections will be only conducted with a written letter or
verbal approval from the water district that provides service to the project. (See
Attached Details)
Hydrants shall be spaced a minimum of 500 feet
apart.
A final copy of the codes, covenants, and
restrictions shall be submitted to this office previous to final acceptance of
the subdivision. The CC & R’s shall contain the following as they apply:
Their shall be no parking of vehicles on an any
roadways where parking is prohibited. The fire department may enforce no
parking regulations by issuing citations. The fire department as well as the
homeowners association may enforce no parking regulations by imposing fines and
or towing any vehicle at the owner’s expense. At the request of the fire
department the homeowners association shall be responsible to tow any vehicle
parked in no parking areas. At the request of the fire department the
homeowner’s assn. shall maintain red curbs and “no parking signs”. Areas
designated as “No Parking” may not be changed nor may this regulation be
changed without the approval of the fire district. (See Attached Details)
Open areas and vacant lots shall be maintained in a
fire safe condition. The homeowners association shall be responsible to remove
dead and dry vegetation at least 30 feet from all non-fire resistive
structures. This includes all homes, outbuildings and wooden fences. This
regulation may not be changed without the approval of the fire district.
Areas around fire hydrants shall remain clear. The
homeowner’s assn shall be responsible to remove vegetation, fences, or any
other obstruction that is around or in front of any fire hydrants within the
subdivision. Blue reflective markers shall be maintained. The homeowner’s assn
shall be responsible to maintain all blue reflective markers at fire hydrant
locations within the subdivision. This regulation may not be changed without
the approval of the fire district.
(See Attached Details)
The final plans shall be approved only when stamped
and/or signed by authorized Central Calaveras Fire District personnel.
Final acceptance of the project is subject to inspection
and testing from the Central Calaveras Fire District. 72 hours notice required
previous to inspection and testing.
Community Safety Plans (under construction)
High Severity Zones (under construction)
Attached Details Not Drawn To Scale:
The following are general requirements of the
Central Calaveras Fire Protection district for new commercial building sites.
These comments are for site plans only. Plans submitted for approval shall
represent all requirements that apply. All of the following comments shall be
printed on a comment sheet attached to the plans submitted for approval.
COMMERCIAL BUILDING SITE INFRASTRUCTURE
The minimum number of access roads serving new
commercial buildings shall be determined by the size of the building, the
planned use for the building (Occupancy) and the fire protection proposed for
the building.
Driveways, thruways, entrances and fire access
roads shall be 26 feet in width for commercial buildings 2 stories or less in
height and 28 feet for commercial building 3 stories or more in height.
Vertical clearance shall be 13 feet 6 inches for the width of the road. For the
purpose of this section, roadway width shall mean driving surface. Curb and
gutter is not included in the roadway width. Emergency access roadways shall be
marked with approved signs stating “EMERGENCY FIRE ACCESS ROAD”. All required
roadways, access roads and water supplies for fire protection shall be
installed and made serviceable prior to and during the time of construction. (See
Attached Details)
Access roadways shall extend to within 150 feet of
all portions of the exterior walls of the first story of any building.
There shall be no parking on fire access roadways
34 feet or less in width or in required fire apparatus turnaround areas.
Parking will only be allowed in designated parking areas. Parking will be
allowed on one side of the road on roadway 34 feet to 40 feet. On roadways over
40 feet parking will be allowed on both sides. When the roadway width restricts
parking, “NO PARKING FIRE LANE” signs shall be posted every 200 feet and curbs
to be painted red with “NO PARKING FIRE LANE” stenciled on them. (See
Attached Details)
Driveway, roadway and emergency access roadway
surfaces shall be paved all weather-driving surface capable of supporting a
40,000 lb load, IAW-2001 CFC, Cal. Co. Ord 8.10.
The grade for all roads, streets, private lanes and
driveways shall not exceed 16 percent.
No roadway shall have a horizontal outside radius
curvature of less than 42 feet or a inside radius curvature of more than 27
feet. (See Attached Details)
Turnarounds are required on driveways and dead end
roads as specified. Cul-de-sac radius shall be 42 feet of driving surface. Curb
and gutter is not included in the cul-de-sac radius. If a hammerhead/T is used,
the top of the (T) shall be a minmum of 60 feet in length. Curb and gutter is
not included in the hammerhead length. (See Attached Details)
Dead-end fire apparatus access roads in excess of
150 feet in length shall be provided with an approved turnaround for fire
apparatus.
Gate entrances shall be at least two feet wider
than the width of the traffic lane serving that gate.
All gates providing access from a road to a
driveway or private road shall be located at least 30 feet from the roadway and
open to allow a vehicle to stop without obstructing traffic on that road. Gates
shall be accessible to the fire district by approved electric key switch;
strobe entry, person gate and standard key pad access code.
Bridges designed for major ingress/egress roads
serving commercial buildings shall have a minmum load limit of 80,000 pounds and
be no narrower than the driving portion of the road serving each end.
On site water supply for firefighting shall be as
follows for new commercial buildings. The minimum number of fire hydrants and
amount of available water for commercial buildings shall be determined by the
size of the building, the planned use for the building (Occupancy) and the fire
protection proposed for the building. Fire flow and the number of hydrants for
new commercial buildings shall be no less than those amounts specified in
Appendix III-A of the 1997 Uniform Fire Code. All proposed water supplies shall
come from a reliable source such as fixed underground water
Distribution system or a static water system
equaling or exceeding the National Fire Protection Assn (NFPA Standard 1142)
“Standard on Water Supplies for Suburban and Rural Fire Fighting”. (A reduction
of fire flow is allowed when the building is provided with an approved
automatic sprinkler system, but in no case shall the fire flow be less than
1,500 gallons per minute at 20 pounds residual pressure). The fire flow for the
proposed building shall be determined by the fire district and indicated on the
final approved plans.
Hydrants shall be wet barrel type with two 2 ½ inch
discharges and one 4 ½ inch discharge, with individual valves for each
discharge. (RICH 960 or equivalent). Two way blue reflective pavement markers
shall be placed in the roadway (eight inches from the center line on the
hydrant side) at each hydrant location. The area around the hydrant will be
kept clear of obstructions including fences, trees and shrubs. The center of
the lowest discharge shall be a minimum of 18 inches and a maximum of 24 inches
off the ground. The hydrant shall be a maximum of 2 feet from the driving surface.
Water supply and hydrants to be provided previous to any building construction.
Final acceptance of the water supply system shall be granted only after testing
and inspection by fire district. Water supply system testing and inspections
will only be conducted with a written letter or verbal approval from the water
district that provides service to the project. (See Attached Details)
Hydrants shall be spaced a minimum of 300 feet
apart. One hydrant shall be placed within 40 feet of each fire department
connection when the building is protected by an automatic fire sprinkler
system. Ballards shall be provided to protect appliances from vehicle damage
when necessary.
All new commercial buildings larger than 4,500
square feet shall be protected by an automatic fire sprinkler system per the
edition of NFPA Pamphlet 13. Design and construction to be completed by a
currently licensed C-16 fire sprinkler designer and contractor. Two sets of
plans shall be submitted for review and approval prior to issuance of a
building permit. The system and all control valves shall be monitored by a UL
listed monitoring station. A letter of agreement with the approved private
licensed central monitoring station shall be submitted prior to final
inspection of the project. The design and location of the fire department
connection and placement of control valves shall be approved Ballards shall be
provided to protect appliances from vehicle damage when necessary.
All new commercial buildings larger than 1,500
square feet but smaller than 4,500 square feet shall be protected by an
automatic fire alarm system per the latest edition of NFPA Pamphlet 72. Two
sets of plans shall be submitted for
review and approval prior to issuance of a building permit. The system shall be
monitored by a UL listed central monitoring station. A letter of agreement with
the approved private licensed central monitoring station shall be submitted
prior to final inspection of the project. All new commercial buildings
regardless of their size on other protection measures shall have an automatic
fire alarm system installed when the occupancy classification is A, E, H or I.
Said system shall be tested and approved by a recognized listing agency. The
electronic fire detection system shall be used only for the detection and
warning of fire or life safety systems and no other systems shall be interfaced
to it.
All new commercial buildings regardless of their
size or other protection measures shall have an manual fire alarm system
installed when the occupancy classification is A, E, H or I.
The final plans shall be approved only when stamped
and/or signed by authorized Central Calaveras Fire District personnel.
Final acceptance of the project is subject to
inspection and testing from Central Calaveras Fire Protection District. 72 hour notice required previous to
inspection and testing.
Attached Details not Drawn to Scale:
The following are general requirements of the
Central Calaveras Fire protection District for new commercial buildings. These
comments are for new commercial buildings only. Plans submitted for approval
represent requirements that apply. All of the following comments shall be
printed on a sheet attached to the plans submitted for approval.
Address of the proposed building shall be posted
and visible from the roadway fronting the property. Whenever the numbers on the
building will no be clearly visible the access roadway, the numbers will be
placed at the access roadway and the driveway. Address numbers shall be visible
from both directions of travel on the roadway fronting the property. Said
numbers shall be a minimum 3 inch letter height, 3/8 stroke, reflectorized and
contrast with their background, or may be a minimum 5 inches and contrast with
their background. When more than one address or suite numbers are proposed,
numbers will be required on the front and back doors of each proposed suite.
All new commercial buildings larger than 4,500
square feet shall be protected by an automatic fire sprinkler system per the
latest edition of NFPA Pamphlet 13. Design and construction to be completed by
a currently licensed fire sprinkler designer and contractor. Two sets of plans
shall be submitted for review and approval prior to issuance of a building
permit. The system and all control valves shall be monitored by an approved
private licensed central monitoring station. A letter of agreement with the
approved private licensed central monitoring station shall be submitted prior
to final inspection of the project. The design and location of the fire
department connection and placement of control valves shall be approved.
Ballards shall be provided to protect appliances from vehicle damage when
necessary. All fire sprinkler control valves and related appliances shall be
visibly labeled.
All new commercial buildings larger than 1,500
square feet but smaller than 4,500 square feet shall be protected by an
automatic fire alarm system per the latest edition of NFPA Pamphlet 72. Design
and construction to be completed by a currently licensed fire alarm designer and
contractor. Two sets of plans shall be submitted for review and approval prior
to issuance of a building permit. The system shall be monitored by an approved
private licensed central monitoring station. A letter of agreement with the approved private licensed central
monitoring station shall be submitted prior to the final inspection of the
project. All new commercial buildings regardless of there size or other
protection measures shall have an approved automatic fire alarm system
installed when the occupancy classification is A, E, H or I. Said system shall
be tested and approved by a recognized listing agency. The electronic fire
detection system shall be used only for the detection and warning of fire or
life safety systems and no other shall be interfaced to it.
Provide and maintain an approved manual fire alarm
system per the California Code of Regulations (CCR), which is consistent with
standards by the latest edition of the NFPA. All new commercial buildings
regardless of their size or other protection measures shall have an approved
manual fire alarm system installed when the occupancy classification is A, E, H
or I. Two sets of plans shall be submitted for review and approval prior to
issuance of a building permit. Said system shall be tested and approved by a
recognized listing agency . The manual fire alarm system shall be used for the
warning of fire or life safety, no other systems shall be interfaced to it.
An approved illuminated indicator board shall be
provided at an approved location or locations within more than on building or
zone will be monitored.
Provide and maintain portable fire extinguishers
with a minimum rating of 2A10BC. Maximum travel distance to portable fire
extinguishers shall not exceed 75 feet. In large open areas there shall be one
extinguisher per 3,000 square feet. The maximum travel distance from laundry
rooms shall not exceed 50 feet. One 40BC rated extinguisher shall be provided
in each kitchen area. Fire extinguishers shall be mounted so that the top of
the extinguisher is not higher than 5 feet from the ground. Fire extinguishers
shall be currently serviced when installed, serviced every 6 years, serviced
after each use and inspected every six months.
Provide an approved hood extinguishing for cooking
surfaces in all commercial building kitchens per NFPA Pamphlet 96. Two sets of
plans and specifications shall be submitted to this office for review and
approval prior to construction.
Approved access shall be provided to all sprinkler,
alarm or other system components that will be utilized in the event of an
emergency. An application must be obtained from the fire district to purchase
access devices.
Hazards and hazardous materials shall be identified
by approved regulatory safety signs that meet the latest edition of NFPA. Fire
protection devices or other components that will be utilized in the event of an
emergency shall be marked in an approved manner. Areas to be labeled with 4 inch letters contrasting with the
background to assure good visibility.
Provide approved panic hardware at all required exit doors. Flush, edge or surface bolts or any other type of device that may be used to close or restrain the doors other than operation of the panic hardware locking device are prohibited. Provide appropriate illuminated exits signs at all required exits. Exit and exit directional signs shall be electrically illuminated and two lamps shall be energized from a separate circuits, one of which shall be used only for such signs, separated from all other circuits in the building an independently controlled. “This Door To Remain Unlocked During Business Hours” to be labeled above all required exit doors. Provide exits signs at every required exit doorway and wherever otherwise required to clearly indicate that direction of egress, an exit sign with letters having a principle stroke not less than ¾ inches wide and at least 6 inches high.
Maximum occupant load sign must be posted in a
conspicuous place near the main exit.
A Knox Box shall be provided for access keys, maps,
MSDS or other applicable items.
A. Current district Knox Box Information Dated:
Tuesday, March 13th 2007 as follows:
1. M-24 Ranch Subdivision (*North & *South
Entrances)
2. Rail Road Flat Elementary School
3. Mountain Ranch Youth Alliance (*Ball Park Area)
4. McCarthy Reservoir Road/Eagle Ranch Airport
(*Rail Road Flat)
B. District Knox Box Key Distribution List dated:
Friday, June 30th 2006
1. Cal-Fire/CDF’s Battalion Chief-4411, Key #: 2
issued May 24th 2002
2. Cal-Fire/CDF’s Battalion Chief-4413, Key #: 3
issued May 24th 2002
3. Cal-Fire/CDF’s Engine-4473, Key #: 1 issued May
24th 2002
4. Calaveras County Sheriff’s Dept (40-keys, Issued
prior to January 12th 2006) Point of Contact: Sgt Tim Sturm,
Calaveras County Sheriff’s Patrol Division @ (209) 754-6500 or Sgt Sturm’s
email @: Tsturm@co.calaveras.ca.us
5. All Central Calaveras Fire Rescue Fire Apparatus
(14), plus extras keys located in the administration’s office safe!
The final plans shall be approved only when stamped
and/or signed by authorized Central Calaveras Fire District personnel.
Final acceptance of the project is subject to inspection and testing from the Central Calaveras Fire District. 72 hour notice required previous to inspection and testing.
The following are general requirements of the
Central Calaveras Fire Protection District for improvements to existing
buildings. These comments are for the improvement of existing commercial
buildings only. Plans submitted for approval shall represent all requirements
that apply. All of the following comments shall be printed on a comment
sheet attached to the plans submitted for approval.
Address
The address of the proposed building shall be
posted and visible from the roadway fronting the property. Whenever the numbers
on the building will not be clearly visible from the access roadway, the
numbers will be placed at the access roadway and the driveway. Address numbers
shall be visible from both directions of travel on the roadway fronting the
property. Said numbers shall be a minimum 3 inch letter height, 3/8 inch
stroke, reflectorized, and contrast with their background, or may be a minimum
5 inches high and contrast with their background. When more than one address or
suite numbers are proposed, numbers will be required on the front and back
doors of each proposed suite.
If alterations impair the operation of an existing
fire sprinkler system, the design and construction to be completed by a
currently licensed C-16 fire sprinkler designer and contractor. The
modifications shall be designed per the latest edition of NFPA Pamphlet 13. Two
sets of plans shall be submitted for review and approval prior to issuance of a
building permit. The system and all control valves shall be monitored by an
approved private licensed central monitoring station. A letter of agreement
with the approved private licensed central monitoring station shall be
submitted prior to the final inspection of the project. The design and location
of the fire department connection and placement of control valves shall be
approved. Ballards shall be provided to protect appliances from vehicle damage
when necessary. All fire sprinkler control valves and related appliances shall
be visibly labeled.
If alterations impair the operation of an existing
fire alarm system, the design and construction to be completed by a currently
licensed fire alarm designer and contractor. The modifications shall be
designed per the latest edition of NFPA Pamphlet 72. Two sets of plans shall be
submitted for review and approval prior to issuance of a building permit. The
system shall be monitored by an approved private licensed central monitoring
station. A letter of agreement with the approved private licensed central
monitoring station shall be submitted prior to final inspection of the project.
All new commercial buildings regardless of their size or other protection
measures shall have an approved automatic fire alarm system installed when the
occupancy classification is A, E, H or I. Said system shall be tested and
approved by a recognized listing agency. The electronic automatic fire
detection system shall be used for only the detection and warning of fire or
life safety systems and no other systems shall be interfaced to it.
Provide and maintain an approved manual fire alarm
system per the California Code of Regulations, which is consistent with
standards by the latest edition of NFPA. All new commercial buildings
regardless of their size or other protection measures shall have an approved
manual fire alarm system installed when the occupancy classification is A, E, H
or I. Two sets of plans shall be submitted for review and approval prior to
issuance of a building permit. Said system shall be tested and approved by a
recognized listing agency. The manual fire alarm system shall be used only for
the warning of fire or life safety, no other systems shall be interfaced to it.
An approved illuminated indicator board shall be
provided at an approved location or locations within more than one building
location or zone will be monitored.
Provide and maintain portable fire extinguishers
with a minimum rating of 2A10BC. Maximum travel distance to portable fire
extinguishers shall not exceed 75 feet. In large open areas there shall be one
extinguisher per 3,000 square feet. The maximum travel distance from laundry
rooms shall not exceed 50 feet. One 40BC rated extinguisher shall be provided
in each kitchen area. Fire extinguishers shall be mounted so that the top of
the extinguisher is not higher than 5 feet from the ground. Fire extinguishers
shall be currently serviced when installed, serviced every 6 years, serviced
after each use, and inspected every six months.
Provide an approved hood extinguishing system for
cooking surfaces in all commercial buildings kitchens per NFPA Pamphlet 96. Two
sets of plans and specifications shall be submitted to this office for review
and approval prior to construction.
Approved access shall be provided to all sprinkler,
alarm or other system components that will be utilized in the event of an
emergency. An application must be obtained from the fire district to purchase
access devices.
Hazards and hazardous materials shall be identified
by approved regulatory safety signs that meet the latest edition of NFPA. Fire
protection devices or other components that will be utilized in the event of an
emergency shall be marked in an approved manner. Areas to be labeled with
4-inch letters contrasting with the background to assure good visibility.
Provide approved panic hardware at all required
exit doors. Flush, edge or surface bolts or any other type of device that may
be used to close or restrain the doors other than operation of the panic
hardware-locking device are prohibited.
Provide appropriate illuminated exits signs at all
required exits. Exit and exit directional signs shall be electrically
illuminated and the two lamps shall be energized from separate circuits, one of
which shall be used only for such signs, separated from all other circuits in
the building and independently controlled.
“This Door To Remain Unlocked During Business
Hours” to be labeled above all required exit doors.
Provide exits signs at every required exit required
exit doorway and wherever otherwise required to clearly indicate that direction
of egress, an exit sign with letters having a principle stroke not less than ¾
inches wide and at least 6 inches high.
Any addition to the square footage of the useable
floor area of an existing building shall require current design features and
codes to be enforced for the entire structure. Site plans will be required.
When any building is modified from its original
intended use, current design features and codes shall be enforced. Site plans
will be required.
The final plans shall be approved only when stamped
and/or signed by authorized Central Cleavers Fire Protection District
personnel.
Final acceptance of the project is subject to
inspection and testing from Central Cleavers Fire District. 72 hour notice
required previous to inspection and testing.
Decorative Materials (under construction)
Emergency lighting (under construction)
1-15,000 square feet $90.00
15, 001- 50,000 square feet $
135.00
50,000 plus square feet $180.00
1-4 units (lot split) $ 45.00
5-30 units
$ 90.00
30 plus units $
180.00
The above fees cover the following services:
Initial review of submitted plans, consultation and
comments
Review of initial re-submittal for approval
Initial on site inspections including, underground
piping, roadways, hydrostatic testing,
Underground pipe flush.
Additional Charges @ $45.00 hr with a one (1) hour
minimum
Any other subsequent re-submittals for changes to
approved plans
Site re-inspections due to changes to approved
plans without approval, hydrostatic test failure, incomplete work and additional
request for inspections.
Any Commercial Building $45.00
Special occupancies I, H, A and R1
1-15,000 square feet $90.00
15,000 – 50,000 square feet $135.00
50,000 plus square feet $180.00
The above fees cover the following services
Initial review of submitted plans, consultation and
comments.
Review of initial re-submittal for approval.
Initial on site inspections
Additional charges @ $45.00 hr with a one (1) hour
minimum
Any other or subsequent re-submittals for changes
to approved plans.
Site re-inspections due to changes to approved
plans without approval, incomplete work and additional requests for
inspections.
1-99 heads $135.00
100-200 heads $180.00
200 plus $180.00 plus per
additional head
The above fees cover the following services:
Initial review of submitted plans, consultation and
comments
Review of initial re-submittal for approval
Initial on site inspections to include, weld
inspection, overhead piping inspection, hydrostatic testing and final
inspection.
Additional charges @ $45.00 hr with a one (1) hour
minimum
Any other or subsequent re-submittals for changes
to approved plans.
Site re-inspections due to changes to approved
plans without approval, hydrostatic test failure, incomplete work and
additional request for inspections.
Any fire alarm system $135.00
The above fees cover the following services:
Initial review of submitted plan, consultation and
comments
Review of initial re-submital for approval
Initial on site inspection, including system test
and final acceptance
Additional charges @ $45.00 hr with a one (1) hour
minimum
Any other or subsequent re-submittals for changes
to approved plans
Site re-inspections due to changes to approved
plans without approval, test failure, incomplete work and additional request
for inspections.
Per Each system $90.00
The above fee covers the following:
Initial review of submitted plans and test for
final approval
Any Commercial Building $45.00
Special occupancies I, H, A and R1
1-15,000 square feet
$90.00
15,000-50,000 square feet $135.00
50,000 plus square feet $180.00
The above fees cover the following services:
Sprinkler plan check for up to 25 heads
Initial review of submitted plans, consultation and
comments
Review of initial re-submittal for approval
Initial on site inspections and final inspection
Addional charges @ $45.00 hr with a one (1) hour
minimum
Any other or subsequent re-submittals for changes
to approved plans
Site re-inspections due to changes to approved
plans without approval, incomplete work and additional request for inspections.
Reports:
Per report/document $ 5.00 for the first page
$.25 for every page thereafter
Exception:
Allied agencies and victims No Charge!
ASSESSOR’S PARCEL NUMBER:
OWNER:
ADDRESS:
FIRE HYDRANTED AREAS:
Residential, Single Family and Multi-Family (Light
Load)
Square feet X .18 w/sprinklers TOTAL:
Commercial and Industrial (Moderate Load)
Square feet x .35 w/sprinklers, .70 w/o sprinklers TOTAL:
Commercial and Industrial (Heavy Load)
Square feet x .53 w/sprinklers, 1.17 w/o sprinklers
TOTAL:
Rural-Non-Hydranted Areas
Residential, Single Family and Multi-Family (Light
Load)
Square feet x .22 w/sprinklers, .43 w/o sprinklers TOTAL:
Commercial and Industrial (Moderate Load)
Square feet x .43 w/sprinklers, .86 w/o sprinklers TOTAL:
Commercial and Industrial (Heavy Load)
Square feet x .65 w/sprinklers, 1.29 w/o sprinklers
TOTAL:
These requirements are for first inspection prior
to the permitting of any structure or new dwelling: Current State Fire Code
states if the driveway slope exceeds 16%, it requires mitigation to allow
40,000 lb emergency vehicle access IAW-2001CFC, Cal. Co Ord. 8.10. 21% is
totally unacceptable in any case. Each inspection would be site specific
and separate from any other parcel. *The correspondence/letter shall include:
Property’s Owner Name:
Site Address:
Assessor’s Parcel (APN) Number/Permit #:
Date of Inspection:
Improvements: What they did to
the driveway to make it comply with emergency access requirements, such as
concreting or asphalting driveway.
Email Dated: Monday, March 12th
2007, from Cathryne Darmer, Calaveras Bldg Dept Cdarmer@co.calaveras.ca.us
Since 1999, proudly serving the Calaveras County
communities of Glencoe, Rail Road Flat, Eagle Ranch Airport, Mountain Ranch and
Sheep Ranch.
Dated: Tuesday, March 13th 2007